TI71M01D06-01EN 3rd Edition: 2012.12.01
#parameter/#monitor Display A, B Function
The #parameter/#monitor display A, B function operates regardless of the operating mode.
The #parameter/#monitor display A, B function periodically notifies #parameter/#monitor
values that are set. The refresh cycle is approximately 10 msec. The parameter/monitor
numbers when the power is turned ON are 375 for A and 376 for B.
To change the #parameter/#monitor numbers to be displayed, first the CC-Link master station
turns ON the IN_MON_A_CHNG_REQ or IN_MON_B_CHNG_REQ signal after setting the
#parameter/#monitor number to be changed in the IN_MON_A_PRM_NO or
IN_MON_B_PRM_NO signal. The drive performs processing to change #parameter/#monitor
numbers to be displayed, turns ON the OUT_MON_A_CHNG_END or
OUT_MON_B_CHNG_END signal, and notifies that the change processing has been
complete. If the change processing completed normally, the drive turns ON the
OUT_MON_A_CHNG_END or OUT_MON_B_CHNG_END signal as well as the
OUT_MON_A_CHNG_OK or OUT_MON_B_CHNG_OK signal. If the change processing did
not complete normally, the OUT_MON_A_CHNG_OK or OUT_MON_B_CHNG_OK signal
stays OFF when the drive turns ON the OUT_MON_A_CHNG_END or
OUT_MON_B_CHNG_END signal.
No inquiry
When write processing completed normally: ON
When write processing did not complete normally: OFF
Notify the values corresponding to
#parameter/#monitor numbers
before change
Notify the values corresponding to
#parameter/#monitor numbers
after change
No inquiry
IN_MON_*_CHNG_REQ
IN_MON_*_PRM_NO
OUT_MON_*_DATA (High,
Low)
ON
OFF
ON
OUT_MON_*_CHNG_END
OUT_MON_*_CHNG_OK
OFF
ON
OFF