09
Bit 9
ON
OFF
-
10
Bit 10
ON
OFF
-
11
Bit 11
ON
OFF
-
12
Bit 12
ON
OFF
-
13
Bit 13
ON
OFF
-
14
Bit 14
ON
OFF
-
15
Bit 15
ON
OFF
-
Dependency:
See also: p2099
p2098[0...1]
Inverter connector-binector converter binector output / Con/bin outp inv
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2468, 9360
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description:
Setting to invert the individual binector outputs of the connector-binector converter.
Using p2098[0], the signals of connector input p2099[0] are influenced.
Using p2098[1], the signals of connector input p2099[1] are influenced.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Bit 0
Inverted
Not inverted
-
01
Bit 1
Inverted
Not inverted
-
02
Bit 2
Inverted
Not inverted
-
03
Bit 3
Inverted
Not inverted
-
04
Bit 4
Inverted
Not inverted
-
05
Bit 5
Inverted
Not inverted
-
06
Bit 6
Inverted
Not inverted
-
07
Bit 7
Inverted
Not inverted
-
08
Bit 8
Inverted
Not inverted
-
09
Bit 9
Inverted
Not inverted
-
10
Bit 10
Inverted
Not inverted
-
11
Bit 11
Inverted
Not inverted
-
12
Bit 12
Inverted
Not inverted
-
13
Bit 13
Inverted
Not inverted
-
14
Bit 14
Inverted
Not inverted
-
15
Bit 15
Inverted
Not inverted
-
Dependency:
See also: r2094, r2095, p2099
p2099[0...1]
CI: Connector-binector converter signal source / Con/bin s_s
Access level: 3
Calculated: -
Data type: Unsigned32 /
Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2468, 9360
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency:
See also: r2094, r2095
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
763
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......