Note
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p8991
USB memory access / USB mem acc
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
1
Max:
2
Factory setting:
1
Description:
Selects the storage medium for access via the USB mass storage.
Value:
1:
Memory card
2:
Flash r/w internal
Note
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p8999
USB functionality / USB Fct
Access level: 4
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
1
Max:
3
Factory setting:
3
Description:
Setting the USB functionality.
Value:
1:
USS commissioning via the virtual COM port
2:
Only memory access
3:
USB commissioning and memory access
Note
COMM: Commissioning.
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p9400
Safely remove memory card / Mem_card rem
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
100
Factory setting:
0
Description:
Setting and display when memory card is "removed safely".
Procedure:
Setting p9400 = 2 results in a value of 3
--> The memory card can be removed safely. After removal the value sets itself to 0 automatically.
Setting p9400 = 2 results in a value of 100
--> The memory card cannot be removed safely. Removal may destroy the file system on the memory card. It may be
necessary to set p9400 = 2 again.
Value:
0:
No memory card inserted
1:
Memory card inserted
2:
Request "safe removal" of the memory card
3:
"Safe removal" possible
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
887
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......