p29626[0...n]
Cavitation protection threshold / Cavi thresh
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: -
Min:
0.00 [%]
Max:
200.00 [%]
Factory setting:
40.00 [%]
Description:
Defines the feedback threshold (as a percentage) for triggering a fault/alarm.
p29627[0...n]
Cavitation protection time / Cavi time
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
1 [s]
Max:
65000 [s]
Factory setting:
30 [s]
Description:
Sets the time for which cavitation conditions have to be present before a fault/alarm is triggered.
r29629.0...2
CO/BO: Status word: application / App status word
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word for application:
bit 0:
= 1, pipe filling is active;
= 0, pipe filling is not active.
bit 2/1:
= 0/1, condesation protection is active;
= 1/1, frost protection is active;
= 0/0, frost and condensation protections are not active;
= 1/0, not used.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Pipe filling
Active
Inactive
-
01
Condensation protection
Active
Inactive
-
02
Frost protection
Active
Inactive
-
p29630
Keep-running operation enable / KeepRun
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the signal source to enable converter keep-running operation. This attempts to prevent the converter from
tripping by enabling all possible existing de-rating features and the automatic restart function.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
929
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......