Description:
Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency:
See also: p1106
WARNING
The minimum speed is preassigned to 20% of the rated motor speed.
After all of the enable signal have been switched on, with the appropriate direction specified, the motor accelerates to
this minimum speed.
NOTICE
The effective minimum speed is formed from p1080 and p1106.
Note
The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
p1081
Maximum speed scaling / n_max scal
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 3050, 3095
Min:
100.00 [%]
Max:
105.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the scaling for the maximum speed (p1082).
For a higher-level speed control, this scaling allows the maximum speed to be briefly exceeded.
Dependency:
See also: p1082
NOTICE
Continuous operation above a scaling of 100 % is not permitted.
p1082[0...n]
Maximum speed / n_max
Access level: 1
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: C2(1), T
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3020, 3050,
3070
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
1500.000 [rpm]
Description:
Sets the highest possible speed.
Example:
Induction motor p0310 = 50 / 60 Hz without output filter and Blocksize power unit
p1082 <= 60 x 240 Hz / r0313 (vector control)
p1082 <= 60 x 550 Hz / r0313 (U/f control)
Dependency:
For vector control, the maximum speed is restricted to 60.0 / (8.333 x 500 µs x r0313). This can be identified by a
reduction in r1084. p1082 is not changed in this process due to the fact that the operating mode p1300 can be changed
over.
If a sine-wave filter (p0230 = 3) is parameterized as output filter, then the maximum speed is limited corresponding to
the maximum permissible filter output frequency (refer to the filter data sheet). When using sine-wave filters (p0230
= 3, 4), the maximum speed r1084 is limited to 70% of the resonant frequency of the filter capacitance and the motor
leakage inductance.
For reactors and dU/dt filters, it is limited to 120 Hz / r0313.
See also: p0230, r0313, p0322
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
625
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......