p1113[0...n]
BI: Setpoint inversion / Setp inv
G120X_USS
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2441, 2442,
2505, 3040
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to invert the setpoint.
Dependency:
See also: r1198
CAUTION
If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using p1113
when the technology controller is enabled because this can cause the speed to change suddenly and lead to positive
couplings in the control loop.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r1114
CO: Setpoint after the direction limiting / Setp after limit
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 3001, 3040,
3050
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Displays the speed/velocity setpoint after the changeover and limiting the direction.
r1119
CO: Ramp-function generator setpoint at the input / RFG setp at inp
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 3050, 3070,
6300, 8022
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Displays the setpoint at the input of the ramp-function generator.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
The setpoint is influenced by other functions, e.g. skip (suppressed) speeds, minimum and maximum limits.
p1120[0...n]
Ramp-function generator ramp-up time / RFG ramp-up time
Access level: 1
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1), T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
999999.000 [s]
Factory setting:
10.000 [s]
Description:
The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the maximum speed
(p1082) in this time.
Dependency:
See also: p1082, p1123
Parameters
7.2 Parameter list
SINAMICS G120X converter
632
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......