Procedure, FSA ... FSC
1. Prepare a cutout and holes in the control cabinet panel for the push-through mounting kit.
Dimension drawings and drill patterns (Page 64)
2. Fix the U-shape frame to the converter using screws (4 × M4 - 2.5 Nm) (step
①
).
3. Push the converter heatsink through the cutout of the control cabinet.
4. Fix the converter to the cabinet panel with screws (FSA/FSB: 6 × M6 - 2.5 Nm; FSC: 6 × M6
- 3 Nm) (step
②
).
You have correctly installed the converter with the push-through mounting kit.
❒
Procedure, FSD ... FSG
1. Prepare a cutout and holes in the control cabinet panel for the push-through mounting kit.
Dimension drawings and drill patterns (Page 64)
2. Fix the top and bottom frames (bearing "TOP" and "BOTTOM" marks respectively) to the
converter using screws (FSD/FSE: 8 × M5 - 3 Nm; FSF/FSG: 8 × M8 - 25 Nm) (step
①
).
Description
2.6 Optional components
SINAMICS G120X converter
42
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......