Without EMC category
Table 4-5
Maximum permissible motor cable length
1)
Converter frame
size
400 V
Maximum motor cable length
With shiel‐
ded motor
cable
Without output
reactor or dv/dt
filter
FSA … FSC
150 m
FSD … FSE
200 m
FSF … FSG
300 m
FSH … FSJ
150 m
With 2 output
reactors in ser‐
ies
FSD … FSE
350 m
FSF … FSG
525 m
With 1 output
reactor
FSH … FSJ
300 m
With dv/dt filter FSD … FSE
350 m
FSF … FSG
650 m
FSH … FSJ
300 m
With sine-wave
filter
FSA … FSF
200 m
FSG
300 m
With un‐
shielded
motor cable
Without output
reactor or dv/dt
filter
FSA … FSC
300 m
FSD … FSE
300 m
FSF … FSG
450 m
FSH … FSJ
200 m
With 2 output
reactors in ser‐
ies or dv/dt filter
FSD … FSE
525 m
FSF … FSG
800 m
With 1 output
reactor or dv/dt
filter
FSH … FSJ
450 m
With sine-wave
filter
FSA … FSF
300 m
FSG
450 m
1)
The values are valid for a pulse frequency set at the factory
690 V converter
EMC category according to EN 61800‑3
Shielded motor cables and EMC-compliant installation are required in order to satisfy an EMC
category.
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
85
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......