Note
When changing p0756, the parameters of the scaling characteristic (p0757, p0758, p0759, p0760) are overwritten with
the following default values:
For p0756 = 0, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 1, p0757 is set to 2.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 2, p0757 is set to 0.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 3, p0757 is set to 4.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 6, 7, p0757 is set to 0 °C, p0758 = 0.0 %, p0759 = 100 °C and p0760 = 100.0 %.
X202: IO module terminal
p0756[0...3]
CU analog inputs type / CU AI type
G120X_DP,
G120X_USS
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9566, 9568,
9576
Min:
0
Max:
10
Factory setting:
[0] 4
[1] 4
[2] 8
[3] 8
Description:
Sets the type of analog inputs.
p0756[0...1] = 0, 1, 4 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
p0756[0...2] = 2, 3 corresponds to a current input (r0752, p0757, p0759 are displayed in mA).
p0756[2...3] = 6, 7, 10 corresponds to a resistor input for temperature measurement (r0752, p0757, p0759 are
displayed in °C).
p0756[2...3] = 8 No temperature sensor connected. Mode for deactivating sensor monitoring (alarm A03520).
In addition, the associated DIP switch must be set.
For the voltage input, DIP switch AI0/1 must be set to "U".
For the current input, DIP switch AI0/1 or AI2 must be set to "I".
For the temperature input, DIP switch AI2 must be set to "TEMP".
Value:
0:
Unipolar voltage input (0 V ... +10 V)
1:
Unipolar voltage input monitored (+2 V ... +10 V)
2:
Unipolar current input (0 mA ... +20 mA)
3:
Unipolar current input monitored (+4 mA to +20 mA)
4:
Bipolar voltage input (-10 V ... +10 V)
6:
Temperature sensor LG-Ni1000
7:
Temperature sensor PT1000
8:
No sensor connected
10:
Temperature sensor DIN Ni 1k (6180 ppm / K)
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Dependency:
See also: A03520
WARNING
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
If the system is operated when the load resistor is switched on (DIP switch set to "I"), the voltage between differential
inputs AI+ and AI- must not exceed 10 V or the injected 80 mA current otherwise the input will be damaged.
Parameters
7.2 Parameter list
SINAMICS G120X converter
568
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......