r5600
Pe energy-saving mode ID / Pe mode ID
G120X_PN
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2381, 2382
Min:
0
Max:
255
Factory setting:
-
Description:
Displays the PROFIenergy mode ID of the effective energy-saving mode.
Value:
0:
POWER OFF
2:
Energy-saving mode 2
240:
Operation
255:
Ready
Note
Pe: PROFIenergy profiles
p5602[0...1]
Pe energy-saving mode pause time minimal / Pe mod t_pause min
G120X_PN
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2381
Min:
300000 [ms]
Max:
4294967295 [ms]
Factory setting:
[0] 300000 [ms]
[1] 480000 [ms]
Description:
Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, time of minimum stay
Index:
[0] = Reserved
[1] = Mode 2
Note
It is not permissible that the value is less than the sum of the "energy-saving mode transition time" and the "operating
state transition time" (system properties).
Pe: PROFIenergy profiles
p5606[0...1]
Pe energy-saving mode time of maximum stay / Pe t_max_stay
G120X_PN
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2381
Min:
0 [ms]
Max:
4294967295 [ms]
Factory setting:
4294967295 [ms]
Description:
Sets the time of maximum stay for the energy-saving mode.
Index:
[0] = Reserved
[1] = Mode 2
Note
Pe: PROFIenergy profiles
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
857
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......