p2396[0...n]
Hibernation mode max. shutdown time / Hib t_off max
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 7038
Min:
0 [s]
Max:
863999 [s]
Factory setting:
0 [s]
Description:
Sets the maximum shutdown time for the "Hibernation mode" function.
If the drive is in the hibernation mode (pulse inhibit) then it is switched on again at the latest after the maximum switch-
off time has expired. If the restart conditions are fulfilled earlier, then the drive is correspondingly switched on earlier.
DANGER
The drive automatically powers itself up at the latest after the maximum switch-off time has expired.
CAUTION
Once the maximum shutdown time has expired, the drive switches itself on automatically and accelerates to the start
speed. The technology controller only becomes effective again when this speed is reached (for p2398 = 1).
Depending on the application, for instance for pumps, it should be ensured that as a result of cyclic starts the tank does
not overflow or for compressors, an overpressure condition does not occur.
Note
Automatic restart once the maximum OFF time has elapsed is deactivated by setting p2396 = 0 s.
r2397[0...1]
CO: Hibernation mode output speed actual / Hib n_outp act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 7038
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Display and connector output for the actual output speed for the "hibernation mode" function.
Note
Zero is displayed if the boost or starting speed is not active.
p2398
Hibernation mode operating type / Hib mode op_type
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7038
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the operating mode for the "Hibernation mode" function.
Value:
0:
Hibernation mode inhibited
1:
Hibernation mode activated
Dependency:
See also: p2200, p2251
See also: A07325
CAUTION
When the "hibernation mode" function is active, the motor can start again automatically.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
823
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......