p0860
BI: Line contactor feedback signal / Line contact feedb
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2634
Min:
-
Max:
-
Factory setting:
863.1
Description:
Sets the signal source for the feedback signal from the line contactor.
Recommendation:
When the monitoring is activated (BI: p0860 not equal to r0863.1), then to control the line contactor, signal BO: r0863.1
of its own drive object should be used.
Dependency:
See also: p0861, r0863
See also: F07300
NOTICE
The line contactor monitoring is deactivated if the control signal of the particular drive object is set as the signal source
for the feedback signal of the line contactor (BI: p0860 = r0863.1).
Note
The state of the line contactor is monitored depending on signal BO: r0863.1.
When the monitoring is activated (BI: p0860 not equal to r0863.1), fault F07300 is then also output if the contactor is
closed before it is controlled using r0863.1.
p0861
Line contactor monitoring time / LineContact t_mon
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2634
Min:
0 [ms]
Max:
5000 [ms]
Factory setting:
100 [ms]
Description:
Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
Dependency:
See also: p0860, r0863
See also: F07300
Note
The monitoring function is disabled for the factory setting of p0860.
r0863.0...1
CO/BO: Drive coupling status word/control word / CoupleZSW/STW
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the status word and control word of the drive coupling.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Closed-loop control operation
Yes
No
-
01
Energize contactor
Yes
No
2634
Note
For bit 01:
Bit 1 is used to control an external line contactor.
Parameters
7.2 Parameter list
SINAMICS G120X converter
594
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......