p1213[0...1]
Automatic restart monitoring time / AR t_monit
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.0 [s]
Max:
10000.0 [s]
Factory setting:
[0] 60.0 [s]
[1] 0.0 [s]
Description:
Sets the monitoring time of the automatic restart (AR).
Index:
[0] = Restart
[1] = Reset start counter
Dependency:
See also: p1210, r1214
NOTICE
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
After fault F07320 occurs, the switch-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
Note
For index 0:
The monitoring time starts when the faults are detected. If the automatic acknowledgments are not successful, the
monitoring time runs again. If, after the monitoring time has expired, the drive has still not successfully started again
(flying restart and magnetizing of the motor must have been completed: r0056.4 = 1), then fault F07320 is output.
The monitoring is deactivated with p1213 = 0. If p1213 is set lower than the sum of p1212, the magnetizing time p0346
and the additional delay time due to the flying restart, then fault F07320 is generated at each restart. If, for p1210 = 1,
the time in p1213 is set lower than in p1212, then fault F07320 is also generated at each restart.
The monitoring time must be extended if the faults that occur cannot be immediately and successfully acknowledged
(e.g. for faults that are permanently present).
In the case of p1210 = 14, 16, the faults which are present must be acknowledged manually within the time in p1213[0].
Otherwise, fault F07320 is generated after the set time.
For index 1:
The start counter (refer to r1214) is only set back to the starting value p1211 if, after successful restart, the time in
p1213[1] has expired. The delay time is not effective for fault acknowledgment without automatic restart (p1210 = 1).
After a power failure (blackout) the delay time only starts after the line supply returns and the Control Unit boots. The
start counter is set to p1211, if F07320 occurred, the switch-on command is withdrawn and the fault is acknowledged.
The start counter is immediately updated if the starting value p1211 or the mode p1210 is changed.
For p1210 = 26, the fault must have been successfully acknowledged and the switch-on command issued within the
time in p1213[0]. Otherwise, fault F07320 is generated after the set time.
r1214.0...15
CO/BO: Automatic restart status / AR status
Access level: 4
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status of the automatic restart (AR).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization
Yes
No
-
01
Wait for alarm
Yes
No
-
02
Auto restart act
Yes
No
-
03
Setting the acknowledgment command
Yes
No
-
04
Acknowledge alarms
Yes
No
-
05
Restart
Yes
No
-
06
Delay time running after automatic switch-on
Yes
No
-
07
Fault
Yes
No
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
650
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......