6.3.4.4
The converter as Ethernet node
Integrating a converter into an Ethernet network (assigning an IP address)
Procedure
1. Set p8924 (PN DHCP mode) = 2 or 3
– p8924 = 2: The DHCP server assigns the IP address based on the MAC address of the
converter.
– p8924 = 3: The DHCP server assigns the IP address based on the device name of the
converter.
2. Save the settings with p8925 = 2. The next time that the converter switches on, it retrieves
the IP address, and you can address the converter as Ethernet node.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EtherNet/IP command "Set Attribute Single" (class F5 hex, attribute 3).
The following options are available:
● via an EtherNet/IP controller
● via an EtherNet/IP commissioning tool
You have now integrated the converter into Ethernet
Displays
r8930: Device name of the converter
r8934: Operating mode, PN or DHCP
r8935: MAC address
Additional information
You can find information about parameters and messages (A08565) in the parameter list.
Parameters (Page 467)
Additional options of integrating converters into Ethernet
You also have the option of integrating the converter into Ethernet using Proneta or STEP 7, for
example.
Here is the example of the "Edit Ethernet station" screen form from Step 7, which you can use
to make the required settings.
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
241
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......