16
Short motor identification (lower quality)
Yes
No
-
17
Measurement without control parameter calculation
Yes
No
-
18
After motID direct transition into operation
Yes
No
-
19
After MotID automatically save results
Yes
No
-
20
Estimate cable resistance
Yes
No
-
21
Calibrating the output voltage measurement
Yes
No
-
22
Only identify circle
Yes
No
-
23
Deactivate circle identification
Yes
No
-
24
Circle identification with 0 and 90 degrees
Yes
No
-
26
Measure with long cable
Yes
No
-
Dependency:
See also: r3925
Note
The parameter is a copy of p1909.
r3928[0...n]
Rotating measurement configuration / Rot meas config
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Successfully completed component of the last rotating measurement carried out.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Saturation characteristic identification
Yes
No
-
02
Moment of inertia identification
Yes
No
-
03
Re-calculates the speed controller parameters
Yes
No
-
04
Speed controller optimization (vibration test)
Yes
No
-
05
q leakage inductance ident. (for current controller adaptation) Yes
No
-
11
Do not change the controller parameters during the
measurement
Yes
No
-
12
Measurement shortened
Yes
No
-
13
After measurement direct transition into operation
Yes
No
-
14
Calculate speed actual value smoothing time
Yes
No
-
Dependency:
See also: r3925
Note
The parameter is a copy of p1959.
r3929[0...n]
Motor data identification modulated voltage generation / MotID U_gen mod
Access level: 4
Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Configuration of voltage generation for the various MotID sections in the case of the most recent successful MotID.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Wobble U_generate to determine dead-time correction
Yes
No
-
01
Wobble U_generate to determine stator resistance
Yes
No
-
02
Wobble U_generation to determine rotor time constant
Yes
No
-
03
Wobble U_generation to determine leakage inductance
Yes
No
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
848
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......