Function description
Table 4-1
Converter operated on a TN system
Converter
Line supply with grounded neutral
Line supply with grounded phase conduc‐
tor and a voltage ≤ 600 V phase to phase
Frame size
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J
Without line
filter
✓
✓
✓
✓
✓
✓
○
○
○
✓
✓
✓
✓
✓
✓
○
○
○
Integrated
line filter C2
✓
✓
✓
✓
✓
✓
✓
○
○
-
-
-
-
-
-
✓
1)
○
○
Integrated
line filter C3
○
○
○
○
○
✓
✓
✓
✓
○
○
○
○
○
-
✓
1)
✓
1)
✓
1)
✓ = Operation permissible
✓
1)
Operation permissible once grounding screw has been removed
If the grounding screw has been removed, the converter no longer fulfills the requirements of class C3.
- Operation not permissible
○ Converter not available
More information on removing the grounding connection in the converter:
Removing functional grounding of the converter (Page 78)
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
76
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC