03
Voltage limiting
Active
Not active
6714
10
Speed adaptation limiting
Active
Not active
-
12
Motor stalled
Yes
No
-
13
Separately excited synchronous motor is excited
Yes
No
-
14
Current model SESM magnetizing excit. current limited to
zero
Yes
No
-
p1416[0...n]
Speed setpoint filter 1 time constant / n_set_filt 1 T
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6020, 6030
Min:
0.00 [ms]
Max:
5000.00 [ms]
Factory setting:
0.00 [ms]
Description:
Sets the time constant for the speed setpoint filter 1 (PT1).
r1438
CO: Speed controller speed setpoint / n_ctrl n_set
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 3001, 6020,
6031
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Display and connector output of the speed setpoint after setpoint limiting for the P component of the speed controller.
For U/f operation, the value that is displayed is of no relevance.
Note
In the standard state (the reference model is deactivated), r1438 = r1439.
r1445
CO: Actual speed smoothed / n_act smooth
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 6040
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Display and connector output for the actual smoothed speed actual value of the speed control.
p1452[0...n]
Speed controller speed actual value smoothing time (sensorless) / n_C n_act T_s SL
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6020, 6040
Min:
0.00 [ms]
Max:
32000.00 [ms]
Factory setting:
10.00 [ms]
Description:
Sets the smoothing time for the actual speed of the speed controller for encoderless closed-loop speed control.
Note
The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the speed
controller must also be increased (e.g. using p0340 = 4).
Parameters
7.2 Parameter list
SINAMICS G120X converter
680
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......