8.1.5
Message for a memory card that is not inserted
Function description
The converter identifies that a memory card is not inserted, and signals this state. The message
is deactivated in the converter factory setting.
Activate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, … 19
2. Set p2119[x] = 2
Message A01101 for a memory card that is not inserted is activated.
❒
To cyclically signal to the higher-level control that a memory card is not inserted, connect
parameter r9401 to the send data of the fieldbus interface.
Deactivate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, … 19
2. Set p2119[x] = 3
Message A01101 for a memory card that is not inserted is deactivated.
❒
Parameter
Parameter
Explanation
Factory setting
p2118[0 … 19]
Change message type, message number
0
p2119[0 … 19]
Change message type, type
0
r9401
Safely remove memory card status
-