Article number
Converter frame size
Rated power (kW)
Line filter
400 V converters
FSA
0.75 … 3
6SL3203-0BE17-7BA0
FSB
4 … 7.5
6SL3203-0BE21-8BA0
FSC
11 … 15
6SL3203-0BE23-8BA0
FSD
18.5 … 37
6SL3203-0BE27-5BA0
FSE
45 … 55
6SL3203-0BE31-1BA0
FSF
75 … 90
6SL3203-0BE31-8BA0
110 ... 132
6SL3203-0BE32-5BA0
FSG
160 … 250
-
FSH
315 ... 400
6SL3760-0MR00-0AA0
FSJ
450 ... 560
690 V converters
FSD
11 ... 37
6SL3000-0BG32-5AA0
FSE
45 ... 55
FSF
75 ... 132
FSH
315 ... 450
6SL3760-0MS00-0AA0
FSJ
500 ... 630
2.6.2
Line reactor
Note
Line reactors are available as optional components for converters of frame sizes FSH and FSJ
only. As the converters of frame sizes FSA to FSG have integrated DC-link chokes, line
reactors are thus not required.
A line reactor is needed for high short-circuit power levels, partly to protect the actual converter
against excessive harmonic currents, and thus against overload, and partly to limit line
harmonics to the permitted values. The harmonic currents are limited by the total inductance
comprising the line reactor and mains supply cable inductance. Line reactors can be omitted if
the mains supply cable inductance is increased sufficiently, i.e., the value of R
SC
must be
sufficiently small.
R
SC
= Relative Short-Circuit power: ratio of short-circuit power S
k Line
at the supply connection
point to the fundamental apparent power S
inv
of the connected converters (to IEC 60146-1-1).
Description
2.6 Optional components
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
33
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......