p2025[0...4]
Fieldbus interface BACnet settings / BACnet setting
G120X_USS
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9310
Min:
0
Max:
4194303
Factory setting:
[0] 1
[1] 5
[2] 3
[3] 32
[4] 0
Description:
Sets the parameter for communication via BACnet.
p2025[0]:
Device object instance number (0 ... 4194303).
p2025[1]:
Maximum number of info frames (1 ... 10).
p2025[2]:
Number of APDU retries (0 ... 39).
p2025[3]:
Maximum master address (1 ... 127).
Index:
[0] = Device object instance number
[1] = Maximum number of info frames
[2] = Number of APDU retries
[3] = Maximum master address
[4] = Reserved
Dependency:
See also: p2030
p2026[0...74]
Fieldbus interface BACnet COV increment / BACnet COV incr
G120X_USS
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9310
Min:
0
Max:
4194303
Factory setting:
1
Description:
Sets BACnet COV (change of value) increment values.
Parameters
7.2 Parameter list
SINAMICS G120X converter
738
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......