Description:
Sets the tolerance time for line phase monitoring for blocksize power units.
If a line phase fault is present for longer than this tolerance time, then a corresponding fault is output.
Dependency:
See also: F30011
NOTICE
When operating with a failed line phase, depending on the active power, values higher than the default value can either
immediately damage the power unit or damage it over the long term.
Note
For the setting p1822 = maximum value, line phase monitoring is deactivated.
p1825
Converter valve threshold voltage / Threshold voltage
Access level: 4
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.0 [Vrms]
Max:
100.0 [Vrms]
Factory setting:
0.6 [Vrms]
Description:
Sets the threshold voltage drop of the valves (power semiconductor devices) to be compensated.
Note
The value is automatically calculated in the motor data identification routine.
p1828
Compensation valve lockout time phase U / Comp t_lock ph U
Access level: 4
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [µs]
Max:
3.99 [µs]
Factory setting:
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase U.
Note
The value is automatically calculated in the motor data identification routine.
p1828
Compensation valve lockout time phase U / Comp t_lock ph U
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 4
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [µs]
Max:
7.80 [µs]
Factory setting:
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase U.
Note
The value is automatically calculated in the motor data identification routine.
p1829
Compensation valve lockout time phase V / Comp t_lock ph V
Access level: 4
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [µs]
Max:
3.99 [µs]
Factory setting:
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase V.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
715
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......