p8809[0...53]
Identification and Maintenance 4 / I&M 4
G120X_PN
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0000 bin
Max:
1111 1111 bin
Factory setting:
0000 bin
Description:
Parameters for the PROFINET data set "Identification and Maintenance 4" (I&M 4).
This information is known as "Signature".
Dependency:
This parameter is preassigned as standard (see note).
After writing information to p8809, p8805 is automatically set to = 1.
See also: p8805
Note
For p8805 = 0 (factory setting) the following applies:
Parameter p8809 contains the information described below.
For p8809[0...3]:
Contains the value from r9781[0] "SI change tracking checksum functional".
For p8809[4...7]:
Contains the value from r9782[0] "SI change tracking time stamp checksum functional".
For p8809[8...53]:
Reserved.
r8854
PROFINET state / PN state
G120X_PN
Access level: 4
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
255
Factory setting:
-
Description:
State display for PROFINET.
Value:
0:
No initialization
1:
Fatal fault
2:
Initialization
3:
Send configuration
4:
Receive configuration
5:
Non-cyclic communication
6:
Cyclic communications but no setpoints (stop/no clock cycle)
255:
Cyclic communication
r8858[0...39]
PROFINET read diagnostics channel / PN diag_chan read
G120X_PN
Access level: 4
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the PROFINET diagnostics data.
Note
Only for internal Siemens diagnostics.
Parameters
7.2 Parameter list
SINAMICS G120X converter
880
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......