Cause:
The power unit has detected an excessive rate of rise in the overvoltage range.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: rated current of motor much greater than that of power unit.
- power cables are not correctly connected.
- power cables exceed the maximum permissible length.
- power unit defective.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star-delta)
- U/f operation: Increase up ramp.
- U/f operation: Check assignment of rated currents of motor and power unit.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
F30081
Power unit: Switching operations too frequent
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has executed too many switching operations for current limitation.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: rated current of motor much greater than that of power unit.
- power cables are not correctly connected.
- power cables exceed the maximum permissible length.
- power unit defective.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star-delta)
- U/f operation: Increase up ramp.
- U/f operation: Check assignment of rated currents of motor and power unit.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
F30105
PU: Actual value sensing fault
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
At least one incorrect actual value channel was detected on the Power Stack Adapter (PSA).
The incorrect actual value channels are displayed in the following diagnostic parameters.
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
1043
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......