Bit Significance
Explanation
Signal inter‐
connection
in the con‐
verter
Telegram 20
All other tele‐
grams
14 ---
1)
1 = MOP down Reduce the setpoint saved in the motorized po‐
tentiometer.
p1036[0] =
r2090.14
15 CDS bit 0
Reserved
Changes over between settings for different
operation interfaces (command data sets).
p0810 =
r2090.15
1)
If you change over from another telegram to telegram 20, then the assignment of the previous
telegram is kept.
Status word 1 (ZSW1)
Bit Significance
Remarks
Signal inter‐
connection
in the con‐
verter
Telegram 20
All other tele‐
grams
0
1 = Ready for switching on
Power supply switched on; electronics initial‐
ized; pulses locked.
p2080[0] =
r0899.0
1
1 = Ready
Motor is switched on (ON/OFF1 = 1), no fault
is active. With the command "Enable opera‐
tion" (STW1.3), the converter switches on the
motor.
p2080[1] =
r0899.1
2
1 = Operation enabled
Motor follows setpoint. See control word 1,
bit 3.
p2080[2] =
r0899.2
3
1 = Fault active
The converter has a fault. Acknowledge fault
using STW1.7.
p2080[3] =
r2139.3
4
1 = OFF2 inactive
Coast down to standstill is not active.
p2080[4] =
r0899.4
5
1 = OFF3 inactive
Quick stop is not active.
p2080[5] =
r0899.5
6
1 = Switching on inhibited active
It is only possible to switch on the motor after
an OFF1 followed by ON.
p2080[6] =
r0899.6
7
1 = Alarm active
Motor remains switched on; no acknowledge‐
ment is necessary.
p2080[7] =
r2139.7
8
1 = Speed deviation within the tol‐
erance range
Setpoint / actual value deviation within the tol‐
erance range.
p2080[8] =
r2197.7
9
1 = Master control requested
The automation system is requested to accept
the converter control.
p2080[9] =
r0899.9
10 1 = Comparison speed reached or
exceeded
Speed is greater than or equal to the corre‐
sponding maximum speed.
p2080[10] =
r2199.1
11 1 = current or
torque limit
reached
1 = torque limit
reached
Comparison value for current or torque has
been reached or exceeded.
p2080[11] =
r0056.13 /
r1407.7
12 ---
1)
1 = Holding
brake open
Signal to open and close a motor holding
brake.
p2080[12] =
r0899.12
13 0 = Alarm, motor overtemperature --
p2080[13] =
r2135.14
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
210
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......