p2037
PROFIdrive STW1.10 = 0 mode / PD STW1.10=0
G120X_DP,
G120X_PN
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
2
Factory setting:
0
Description:
Sets the processing mode for PROFIdrive STW1.10 "master control by PLC".
Generally, control world 1 is received with the first receive word (PZD1) (this is in conformance to the PROFIdrive
profile). The behavior of STW1.10 = 0 corresponds to that of the PROFIdrive profile. For other applications that deviate
from this, the behavior can be adapted using this particular parameter.
Value:
0:
Freeze setpoints and continue to process sign-of-life
1:
Freeze setpoints and sign-of-life
2:
Do not freeze setpoints
Recommendation:
Do not change the setting p2037 = 0.
Note
If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then p2037
should be set to 2.
p2038
PROFIdrive STW/ZSW interface mode / PD STW/ZSW IF mode
G120X_DP,
G120X_PN
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
2
Factory setting:
0
Description:
Sets the interface mode of the PROFIdrive control words and status words.
When selecting a telegram via p0922 (p2079), this parameter influences the device-specific assignment of the bits in
the control and status words.
Value:
0:
SINAMICS
2:
VIK-NAMUR
Dependency:
See also: p0922, p2079
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
- For p0922 (p2079) = 1, 350 ... 999, p2038 is automatically set to 0.
- For p0922 (p2079) = 20, p2038 is automatically set to 2.
It is not then possible to change p2038.
p2039
Select debug monitor interface / Debug monit select
Access level: 4
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Description:
The serial interface for the debug monitor is COM1 (commissioning interface, RS232) or COM2 (fieldbus interface,
RS485).
Value = 0: Deactivated
Value = 1: COM1, commissioning protocol is deactivated
Value = 2: COM2, field bus is deactivated
Value = 3: Reserved
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
743
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......