Changing parameter values
Table 6-15
Request to change parameters
Data block
Byte n
Bytes n + 1
n
Header
Reference
01 hex ... FF hex
02 hex: Change request
0
01 hex (ID of drive objects, at G120 always = 1) Number of parameters (m)
01 hex ... 27 hex
2
Address, parameter 1
10 hex: Parameter value
Number of indices
00 hex ... EA hex
(00 hex and 01 hex are equivalents)
4
Parameter number
0001 hex ... FFFF hex
6
Number of the 1st index
0001 hex ... FFFE hex
8
…
…
Address, parameter 2
…
…
…
…
Address, parameter m …
Values, parameter 1
Format
02 hex:
Integer 8
03 hex:
Integer 16
04 hex:
Integer 32
05 hex:
Unsigned 8
06 hex:
Unsigned 16
07 hex:
Unsigned 32
08 hex:
Floating Point
0A hex:
Octet String
0D hex:
Time Difference
34 hex
: TimeOfDay without date indication
35 hex
: TimeDifference with date indication
36 hex
: TimeDifference without date indication
41 hex:
Byte
42 hex:
Word
43 hex:
Double word
Number of index values
00 hex ... EA hex
Value of the 1st index
…
Values, parameter 2
…
…
…
Values, parameter m
…
Table 6-16
Response, if the converter has executed the change request
Data block
Byte n
Bytes n + 1
n
Header
Reference (identical to a change request)
02 hex (change request successful)
0
01 hex (ID of drive objects, at G120 always = 1) Number of parameters (identical to a change
request)
2
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
222
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...