Dependency:
See also: p2310, p2311, p2312, p2313, p2314, r2316
Note
Kp adaptation is activated with p2252.7 = 1.
r2316
CO: Technology controller, Kp adaptation output / Kp adapt outp
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
-
Max:
-
Factory setting:
-
Description:
Display and connector output for the output signal of the adaption of proportional gain Kp for the technology controller.
Dependency:
See also: p2252, p2310, p2311, p2312, p2313, p2314, p2315
p2317
CI: Technology controller Tn adaptation input value signal source / Tn adapt inp s_s
Access level: 2
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the input value of the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2252, p2318, p2319, p2320, p2321, r2322
Note
Tn adaptation is activated with p2252.8 = 1.
p2318
Technology controller Tn adaptation upper value / Tn adapt upper val
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
3.000 [s]
Description:
Sets the upper value for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2319, p2320, p2321, r2322
Note
Tn adaptation is activated with p2252.8 = 1.
p2319
Technology controller Tn adaptation lower value / Tn adapt lower val
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
10.000 [s]
Description:
Sets the lower value for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2318, p2320, p2321, r2322
Note
Tn adaptation is activated with p2252.8 = 1.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
811
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......