Converter frame
size
690 V
Maximum motor cable length
With un‐
shielded
motor cable
Without output
reactor or dv/dt
filter
FSD 18.5 kW …
30 kW
300 m
FSD 37 kW …
FSG
450 m
FSH … FSJ
200 m
With 2 output
reactors in ser‐
ies
FSD 18.5 kW …
30 kW
525 m
FSD 37 kW …
FSG
800 m
With 1 output
reactor
FSH … FSJ
450 m
With dv/dt filter FSD 18.5 kW …
30 kW
525 m
FSD 37 kW …
FSG
625 m
2)
800 m
3)
FSH … FSJ
450 m
1)
The values are valid for a pulse frequency set at the factory
2)
At a maximum voltage of 1350 V at the motor terminals
3)
At a maximum voltage of 1500 V at the motor terminals
More information
The permissible length of the motor cable also depends on the quality of the motor cable and
the pulse frequency. The above values apply to high-quality cables, e.g. CY100.
Dimension the motor cable such that the resistance losses are less than 5% of the rated
converter power.
4.1.4
Connecting the converter and converter components
WARNING
Electric shock when the motor terminal box is open
As soon as the converter is connected to the line supply, the motor connections of the
converter may carry dangerous voltages. When the motor is connected to the converter, there
is danger to life through contact with the motor terminals if the motor terminal box is open.
● Close the motor terminal box before connecting the converter to the line supply.
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
87
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......