Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2189 > p2190
See also: p2184, p2190
See also: A07926
Note
The upper envelope curve is defined by p2185, p2187 and p2189.
p2190[0...n]
Load monitoring torque threshold 3 lower / M_thresh 3 lower
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 7_1
Unit selection: p0505
Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2190 < p2189
See also: p2184, p2189
See also: A07926
Note
The lower envelope curve is defined by p2186, p2188 and p2190.
p2191[0...n]
Load monitoring torque threshold no load / M_thresh no load
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 7_1
Unit selection: p0505
Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description:
Setting of the torque threshold to identify dry running operation for pumps or belt breakage for fans.
Dependency:
The following applies: p2191< p2168 if p2168 <> 0
See also: p2181, p2182, p2184, p2193
See also: A07892, F07895, A07926
Note
For the setting p2191 = 0, the monitoring for dry running operation or belt breakage is deactivated.
Pre-assignment: p2191 = 5 % of the rated motor torque (p0333).
p2192[0...n]
Load monitoring delay time / Load monit t_del
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
0.00 [s]
Max:
65.00 [s]
Factory setting:
10.00 [s]
Description:
Sets the delay time to evaluate the load monitoring.
p2193[0...n]
Load monitoring configuration / Load monit config
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
0
Max:
5
Factory setting:
1
Description:
Sets the load monitoring configuration.
Parameters
7.2 Parameter list
SINAMICS G120X converter
788
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......