Note
CDS: Command Data Set
DDS: Drive Data Set
The following control bits are displayed in r0055:
Bit 00: r1198.0
Bit 01: r1198.1
Bit 02: r1198.2
Bit 03: r1198.3
Bit 04: r0837.0
Bit 05: r0837.1
Bit 08: r2349.0 (negated)
Bit 09: r1239.11
Bit 13: r2138.13 (negated)
Bit 15: r0836.1
r0056.0...15
CO/BO: Status word, closed-loop control / ZSW cl-loop ctrl
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2526
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the status word of the closed-loop control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization completed
Yes
No
-
01
De-magnetizing completed
Yes
No
-
02
Pulse enable available
Yes
No
-
04
Magnetizing completed
Yes
No
-
05
Voltage boost when starting
Active
Inactive
6301
06
Acceleration voltage
Active
Inactive
6301
07
Frequency negative
Yes
No
-
08
Field weakening active
Yes
No
-
09
Voltage limit active
Yes
No
6714
10
Slip limit active
Yes
No
6310
11
Frequency limit active
Yes
No
-
12
Current limiting controller voltage output active
Yes
No
-
13
Current/torque limiting
Active
Inactive
6060
14
Vdc_max controller active
Yes
No
6220,
6320
15
Vdc_min controller active
Yes
No
6220,
6320
r0060
CO: Speed setpoint before the setpoint filter / n_set before filt.
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 2701, 6030,
6799, 6822
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Displays the actual speed setpoint at the input of the speed controller or U/f characteristic (after the interpolator).
Dependency:
See also: r0020
Parameters
7.2 Parameter list
SINAMICS G120X converter
490
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......