Note
The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5
For p0500 = 1 and when the calculation is initiated, the following parameters are set:
- p1570 = 100 %
- p1580 = 0 % (no efficiency optimization)
- p1574 = 2 V
- p1750.2 = 0
- p1802 = 9 or 19 (optimized pulse pattern for p0300 = 14)
- p1803 = 106 %
For p0500 = 3 and when the calculation is initiated, the following parameters are set:
- p1570 = 103 % (flux boost for full load)
- p1580 = 100 % (efficiency optimization)
- p1574 = 2 V
- p1750.2 = 1: Encoderless control of the induction motor is effective down to zero frequency.
- p1802 = 9 or 19 (optimized pulse pattern for p0300 = 14)
- p1803 = 106 %
p0501
Technological application (Standard Drive Control) / Techn appl SDC
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: C2(1), T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0340 = 5.
Value:
0:
Constant load (linear characteristic)
1:
Speed-dependent load (parabolic characteristic)
Dependency:
See also: p1300
NOTICE
If the technological application is set to p0501 = 0, 1 during commissioning (p0010 = 1, 5, 30), the operating mode
(p1300) is pre-set accordingly.
Note
The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5
For p0501 = 0, 1 and when the calculation is initiated, the following parameters are set:
- p1802 = 0
- p1803 = 106 %
- p3855.0 = 1 (DC quantity control on)
For p1802 / p1803:
These parameters are only changed, in all cases, if a sine-wave output filter (p0230 = 3, 4) has not been selected.
p0502
Technological application (Dynamic Drive Control) / Techn appl DDC
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: C2(1), T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
5
Factory setting:
0
Parameters
7.2 Parameter list
SINAMICS G120X converter
538
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......