p3235
Phase failure signal motor monitoring time / Ph_fail t_monit
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [ms]
Max:
2000 [ms]
Factory setting:
320 [ms]
Description:
Sets the monitoring time for phase failure detection of the motor.
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note
For p3235 = 0 the function is deactivated.
The monitoring is automatically deactivated during a flying restart for a motor that is still rotating.
3-phase phase failures cannot be detected and are indicated by other messages (e.g. F07902).
r3313
Efficiency optimization 2 optimum flux / Optimum flux
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: r2004
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6722, 6837
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Displays the calculated, optimum flux.
Dependency:
See also: p1401, p3315, p3316
Note
The function is activated via p1401.14 = 1.
p3315[0...n]
Efficiency optimization 2 minimum flux limit value / Min flux lim val
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6722, 6837
Min:
10.0 [%]
Max:
200.0 [%]
Factory setting:
50.0 [%]
Description:
Sets the minimal limit value for the calculated optimum flux.
Dependency:
See also: p1401, r3313, p3316
Note
The function is activated via p1401.14 = 1.
p3316[0...n]
Efficiency optimization 2 maximum flux limit value / Max flux lim val
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6722, 6837
Min:
10.0 [%]
Max:
200.0 [%]
Factory setting:
110.0 [%]
Description:
Sets the maximum limit value for the calculated optimum flux.
Dependency:
See also: p1401, r3313, p3315
Note
The function is activated via p1401.14 = 1.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
833
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......