Maximum permissible motor cable length (Page 82)
NOTICE
Damage to the output reactor by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using the output reactor is 4 kHz or 2 kHz
(for FSH/FSJ). The output reactor can be damaged if the pulse frequency is exceeded.
● When using an output reactor, the pulse frequency of the converter must not exceed 4 kHz
or 2 kHz (for FSH/FSJ).
NOTICE
Damage to the output reactor if it is not activated during commissioning
The output reactor may be damaged if it is not activated during commissioning.
● Activate the output reactor during commissioning via parameter p0230.
● Activate the output reactor during commissioning according to the electric specifications.
Article number
Converter frame size Rated power (kW)
Output reactor
400 V converters
FSD
18.5
6SL3202-0AE23-8CA0
22 ... 37
6SE6400-3TC07-5ED0
FSE
45 ... 55
6SE6400-3TC14-5FD0
FSF
75 ... 90
110
6SL3000-2BE32-1AA0
132
6SL3000-2BE32-6AA0
FSG
160
6SL3000-2BE33-2AA0
200
6SL3000-2BE33-8AA0
250
6SL3000-2BE35-0AA0
FSH
315
6SL3000-2AE36-1AA0
355 ... 400
6SL3000-2AE38-4AA0
FSJ
450 ... 500
6SL3000-2AE41-0AA0
560
6SL3000-2AE41-4AA0
690 V converters
FSD
3 … 18.5
JTA:TEU2532-0FP00-4EA0
22 … 37
JTA:TEU9932-0FP00-4EA0
FSE
45 … 55
JTA:TEU9932-0FS00-0EA0
FSF
75 … 90
JTA:TEU9932-1FC00-1BA0
110 … 132
JTA:TEU9932-0FV00-1BA0
FSG
160 … 250
JTA:TEU4732-0FA00-0BA0
Description
2.6 Optional components
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
37
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......