p2155[0...n]
Speed threshold 2 / n_thresh val 2
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8010
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
900.00 [rpm]
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
See also: p2140, r2197
p2156[0...n]
On delay comparison value reached / t_on cmpr val rchd
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8010
Min:
0.0 [ms]
Max:
10000.0 [ms]
Factory setting:
0.0 [ms]
Description:
Sets the switch-in delay time for the signal "comparison value reached" (BO: r2199.1).
Dependency:
See also: p2141, p2142, r2199
p2161[0...n]
Speed threshold 3 / n_thresh val 3
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8010, 8011
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
5.00 [rpm]
Description:
Sets the speed threshold value for the signal "|n_act| < speed threshold value 3" (BO: r2199.0).
Dependency:
See also: p2150, r2199
p2162[0...n]
Hysteresis speed n_act > n_max / Hyst n_act>n_max
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8010
Min:
0.00 [rpm]
Max:
60000.00 [rpm]
Factory setting:
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the signal "n_act > n_max" (BO: r2197.6).
Dependency:
See also: r1084, r1087, r2197
NOTICE
For p0322 = 0, the following applies: p2162 <= 0.1 * p0311
For p0322 > 0, the following applies: p2162 <= 1.02 * p0322 - p1082
If one of the conditions is violated, p2162 is appropriately and automatically reduced when exiting the commissioning
mode.
Parameters
7.2 Parameter list
SINAMICS G120X converter
780
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......