p2320
Technology controller Tn adaptation lower starting point / Tn adapt lower pt
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
0.00 [%]
Description:
Sets the lower activation point for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2318, p2319, p2321, r2322
CAUTION
The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note
Tn adaptation is activated with p2252.8 = 1.
p2321
Technology controller Tn adaptation upper starting point / Tn adapt upper pt
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the upper activation point for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2318, p2319, p2320, r2322
CAUTION
The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note
Tn adaptation is activated with p2252.8 = 1.
r2322
CO: Technology controller Tn adaptation output / Tn adapt output
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
- [s]
Max:
- [s]
Factory setting:
- [s]
Description:
Display and connector output for the output signal of the adaption of integral time Tn for the technology controller.
Dependency:
See also: p2252, p2317, p2318, p2319, p2320, p2321
Note
Tn adaptation is activated with p2252.8 = 1.
p2339
Techn. controller threshold value f. I comp. hold for skip speed / Tec_ctrl thr_skip
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: 9_1
Unit selection: p0595
Function diagram: -
Min:
0.00 [%]
Max:
200.00 [%]
Factory setting:
2.00 [%]
Description:
Sets the threshold value for the system deviation of the technology controller, which controls holding the controller
integral component in the range of the skip speeds of the ramp-function generator.
Recommendation:
To avoid speed setpoint steps in the range of the skip speeds, we recommend setting p2252 bit 4 = 1 (ramp-function
generator bypass deactivated).
Parameters
7.2 Parameter list
SINAMICS G120X converter
812
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......