r1198.0...15
CO/BO: Control word setpoint channel / STW setpoint chan
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2505
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the control word of the setpoint channel.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fixed setpoint bit 0
Yes
No
3010
01
Fixed setpoint bit 1
Yes
No
3010
02
Fixed setpoint bit 2
Yes
No
3010
03
Fixed setpoint bit 3
Yes
No
3010
05
Inhibit negative direction
Yes
No
3040
06
Inhibit positive direction
Yes
No
3040
11
Setpoint inversion
Yes
No
3040
13
Motorized potentiometer raise
Yes
No
3020
14
Motorized potentiometer lower
Yes
No
3020
15
Bypass ramp-function generator
Yes
No
3070
r1199.0...8
CO/BO: Ramp-function generator status word / RFG ZSW
Access level: 4
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 3001, 3080
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word for the ramp-function generator (RFG).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ramp-up active
Yes
No
-
01
Ramp-down active
Yes
No
-
02
RFG active
Yes
No
-
03
Ramp-function generator set
Yes
No
-
04
Ramp-function generator held
Yes
No
-
05
Ramp-function generator tracking active
Yes
No
-
06
Maximum limit active
Yes
No
-
07
Ramp-function generator acceleration positive
Yes
No
-
08
Ramp-function generator acceleration negative
Yes
No
-
Note
For bit 02:
The bit is the result of the OR logic operation - bit 00 and bit 01.
p1200[0...n]
Flying restart operating mode / FlyRest op_mode
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6300, 6850
Min:
0
Max:
4
Factory setting:
0
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
643
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...