6.5.2.3
Enable direction of rotation
Function description
S
S
[
\
[
\
W
\
\
[
[
In the factory setting of the converter, the negative direction of rotation of the motor is inhibited.
Set parameter p1110 = 0 to permanently enable the negative direction of rotation.
Set parameter p1111 = 1 to permanently inhibit the positive direction of rotation.
Parameters
Table 6-83
Application examples for inhibiting and enabling the direction of rotation
Number
Name
Factory setting
p1110
BI: Inhibit negative direction
1
p1111
BI: Inhibit positive direction
0
Advanced commissioning
6.5 Setpoints and setpoint processing
SINAMICS G120X converter
340
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC