Description:
Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature in the motor temperature
model 2 (p0612.1 = 1).
Dependency:
For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
See also: p0625
NOTICE
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0629[0...n]
Stator resistance reference / R_stator ref
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00000 [ohm]
Max:
2000.00000 [ohm]
Factory setting:
0.00000 [ohm]
Description:
Reference value for the identification of the stator resistance every time the drive is switched on.
Dependency:
The measurement of the reference value is activated by the automatic calculation (p0340 = 1, 2), if the following
conditions apply:
- the motor temperature is at this instant in time less than 30 °C (r0035).
- a temperature sensor is not being used (p0601).
See also: p0621, r0623
Note
The reference value to identify the stator resistance is determined at the first identification. This must be realized when
the motor is in a cold state, as the value refers to the ambient temperature p0625. The feeder cable resistance should
be entered into p0352 before the measurement.
The result must be saved after the first measurement so that the reference is available after the CU has powered up.
When changing p0350 or p0352, the reference value p0629 should be re-determined.
r0630[0...n]
Mot_temp_mod ambient temperature / Mod T_ambient
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2006
Dynamic index: MDS, p0130
Unit group: 21_1
Unit selection: p0505
Function diagram: 8018
Min:
- [°C]
Max:
- [°C]
Factory setting:
- [°C]
Description:
Displays the ambient temperature of the motor temperature model (models 2 and 3).
r0631[0...n]
Mot_temp_mod stator iron temperature / Mod T_stator
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2006
Dynamic index: MDS, p0130
Unit group: 21_1
Unit selection: p0505
Function diagram: 8018
Min:
- [°C]
Max:
- [°C]
Factory setting:
- [°C]
Description:
Displays the stator iron temperature of the motor temperature model (models 2 and 3).
Note
For motor temperature model 1 (p0612.0 = 1), this parameter is not valid:
Parameters
7.2 Parameter list
SINAMICS G120X converter
556
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......