r0774[0...2]
CU analog outputs output voltage/current actual / CU AO U/I_outp
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9572
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the actual output voltage or output current at the analog outputs.
Index:
[0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Dependency:
See also: p0776
Note
AO: Analog Output
X202: IO module terminal
p0775[0...2]
CU analog outputs activate absolute value generation / CU AO absVal act
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9572
Min:
0
Max:
1
Factory setting:
0
Description:
Activates the absolute value generation for the analog outputs.
Value:
0:
No absolute value generation
1:
Absolute value generation switched in
Index:
[0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Note
AO: Analog Output
X202: IO module terminal
p0776[0...2]
CU analog outputs type / CU AO type
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9572
Min:
0
Max:
2
Factory setting:
0
Description:
Sets the analog output type.
p0776[x] = 1 corresponds to a voltage output (p0774, p0778, p0780 are displayed in V).
p0776[x] = 0, 2 corresponds to a current output (p0774, p0778, p0780 are displayed in mA).
Value:
0:
Current output (0 mA ... +20 mA)
1:
Voltage output (0 V ... +10 V)
2:
Current output (+4 mA ... +20 mA)
Index:
[0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
573
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......