p2901[0...n]
CO: Fixed value 2 [%] / Fixed value 2 [%]
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 1021
Min:
-10000.00 [%]
Max:
10000.00 [%]
Factory setting:
0.00 [%]
Description:
Setting and connector output for a fixed percentage value.
Dependency:
See also: p2900, p2930
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
r2902[0...14]
CO: Fixed values [%] / Fixed values [%]
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 1021
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Display and connector output for frequently used percentage values.
Index:
[0] = Fixed value +0 %
[1] = Fixed value +5 %
[2] = Fixed value +10 %
[3] = Fixed value +20 %
[4] = Fixed value +50 %
[5] = Fixed value +100 %
[6] = Fixed value +150 %
[7] = Fixed value +200 %
[8] = Fixed value -5 %
[9] = Fixed value -10 %
[10] = Fixed value -20 %
[11] = Fixed value -50 %
[12] = Fixed value -100 %
[13] = Fixed value -150 %
[14] = Fixed value -200 %
Dependency:
See also: p2900, p2901, p2930
Note
The signal sources can, for example, be used to interconnect scalings.
p2930[0...n]
CO: Fixed value M [Nm] / Fixed value M [Nm]
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2003
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 1021
Min:
-100000.00 [Nm]
Max:
100000.00 [Nm]
Factory setting:
0.00 [Nm]
Description:
Setting and connector output for a fixed torque value.
Dependency:
See also: p2900, p2901, r2902
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
825
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......