Dependency:
See also: p8925, r8933
Note
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
p8924
PN DHCP Mode / PN DHCP mode
G120X_PN
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Description:
Sets the DHCP mode for the onboard PROFINET interface on the Control Unit.
The actual DHCP mode is displayed in r8934.
Value:
0:
DHCP off
2:
DHCP on, identification using MAC address
3:
DHCP on, identification via name of station
Dependency:
See also: p8925, r8934
NOTICE
When the DHCP mode is active (p8924 not equal to 0), then PROFINET communication via this interface is no longer
possible!
Note
The interface configuration (p8920 and following) is activated with p8925.
The active DHCP mode is displayed in parameter r8934.
The parameter is not influenced by setting the factory setting.
p8925
Activate PN interface configuration / PN IF config
G120X_PN
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Description:
Setting to activate the interface configuration for the onboard PROFINET interface on the Control Unit.
p8925 is automatically set to 0 at the end of the operation.
Value:
0:
No function
1:
Reserved
2:
Activate and save configuration
3:
Delete configuration
Dependency:
See also: p8920, p8921, p8922, p8923, p8924
NOTICE
When the DHCP mode is active (p8924 > 0), then PROFINET communication via this interface is no longer possible!
Note
For p8925 = 2:
The interface configuration (p8920 and following) is saved and activated after the next POWER ON.
For p8925 = 3:
The factory setting of the interface configuration is loaded after the next POWER ON.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
883
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......