p2141[0...n]
Speed threshold 1 / n_thresh val 1
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8010
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
5.00 [rpm]
Description:
Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency:
See also: p2142, r2199
p2142[0...n]
Hysteresis speed 1 / n_hysteresis 1
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8010
Min:
0.00 [rpm]
Max:
300.00 [rpm]
Factory setting:
2.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO: r2199.1).
Dependency:
See also: p2141, r2199
p2144[0...n]
BI: Motor stall monitoring enable (negated) / Mot stall enab neg
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 8012
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the negated enable (0 = enable) of the motor stall monitoring.
Dependency:
See also: p2163, p2164, p2166, r2197, r2198
See also: F07900
Note
When interconnecting the enable signal with r2197.7 then the stall signal is suppressed if there is no speed setpoint -
actual value deviation.
r2145[0...63]
Alarm time received in days / t_alarm recv days
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8065
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the system runtime in days when the alarm occurred.
Dependency:
See also: r2110, r2122, r2123, r2124, r2125, r2134, r2146, p8401
NOTICE
The time comprises r2145 (days) and r2123 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
777
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......