r2379.0...7
CO/BO: Closed-loop cascade control status word / Csc_ctrl ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word of the closed-loop cascade control
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Start external motor 1
Yes
No
-
01
Start external motor 2
Yes
No
-
02
Start external motor 3
Yes
No
-
03
Switch-in motor
Yes
No
-
04
Switch-in/switch-out active
Yes
No
-
05
All motors active
Yes
No
-
06
Automatic replacement not possible
Yes
No
-
07
Alarm active
Yes
No
-
p2380[0...2]
Closed-loop cascade control operating hours / Csc_ctrl op_hrs
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.0 [h]
Max:
340.28235E36 [h]
Factory setting:
0.0 [h]
Description:
Displays the operating hours for the external motors.
The display can only be reset to zero.
Index:
[0] = Motor 1
[1] = Motor 2
[2] = Motor 3
p2381
Closed-loop cascade control max time for continuous operation / Csc_ctrl t_max
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.1 [h]
Max:
100000.0 [h]
Factory setting:
24.0 [h]
Description:
Time limit for the continuous operation of external motors.
Continuous operation is measured starting from when a motor is connected to the line voltage. It ends when a motor
is disconnected from the line.
p2382
Closed-loop cascade control operating time limit / Csc_ctrl t_max op
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.1 [h]
Max:
100000.0 [h]
Factory setting:
24.0 [h]
Description:
Limit for the total operating time of external motors.
The total operating time of an external motor increases every time it is switched in.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
819
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......