r2125[0...63]
Alarm time removed in milliseconds / t_alarm res ms
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8065
Min:
- [ms]
Max:
- [ms]
Factory setting:
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
See also: r2110, r2122, r2123, r2124, r2134, r2145, r2146, p8400
NOTICE
The time comprises r2146 (days) and r2125 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
p2126[0...19]
Change acknowledge mode fault number / Chng ackn F_no
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8075
Min:
0
Max:
65535
Factory setting:
0
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
See also: p2127
Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2127[0...19]
Change acknowledge mode mode / Chng ackn mode
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8075
Min:
1
Max:
2
Factory setting:
1
Description:
Sets the acknowledge mode for selected fault.
Value:
1:
Acknowledgment only using POWER ON
2:
Ack IMMEDIATELY after the fault cause has been removed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
See also: p2126
NOTICE
It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
Parameters
7.2 Parameter list
SINAMICS G120X converter
772
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......