Parameter
Number
Name
Factory setting
r0046.0…31
CO/BO: Missing enable signals
-
p0857
Power unit monitoring time
10000 ms
p0858[C]
BI: Unconditionally close holding brake
0
p0860
BI: Line contactor feedback signal
863.1
p0861
Line contactor monitoring time
100 ms
p1226[D]
Speed threshold for standstill detection
20 rpm
p1227
Standstill detection monitoring time
300 s
p1228
Pulse suppression delay time
0.01 s
For additional information on parameters, please refer to the parameter list.
6.3.2
Adapt the default setting of the terminal strips
Overview
In the converter, the input and output signals are interconnected with specific converter
functions using special parameters. The following parameters are available to interconnect
signals:
● Binectors BI and BO are parameters to interconnect binary signals.
● Connectors CI and CO are parameters to interconnect analog signals.
The following chapters describe how you adapt the function of individual converter inputs and
outputs using binectors and connectors.
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
186
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......