p29530[0...5]
Multi-pump control absolute operating hours / Mpc op_hrs
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [h]
Max:
340.28235E36 [h]
Factory setting:
0.00 [h]
Description:
Displays the total operating hours for motors.
The display can only be reset to zero.
Index:
[0] = Motor 1 operating hours
[1] = Motor 2 operating hours
[2] = Motor 3 operating hours
[3] = Motor 4 operating hours
[4] = Motor 5 operating hours
[5] = Motor 6 operating hours
Note
Absolute operating hours means the total operating hours since the motor's initial operation.
p29531
Multi-pump control maximum time for continuous operation / Mpc t_max
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.01 [h]
Max:
100000.00 [h]
Factory setting:
24.00 [h]
Description:
Time limit for the continuous operation of motors.
Continuous operation is measured starting from when a motor is ON and It ends when a motor is OFF.
p29533
Multi-pump control switch-off sequence / Mpc sw_off seq
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Selection of the response used to stop the motors when the OFF command is sent.
For p29533 = 1:
when OFF1:
In this mode the motors connecting with the mains stop one at a time separated by one ramp down delay in the reverse
order in which they were switched on. The converter controlled motor stops with a normal ramp down (OFF1) which
commences when the first motor connecting with the mains is switched off.
The time set in p29537 is applied as a delay time between the disconnection of each line motor.
Then speed-regulated motor is ramp down following OFF1 behavior.
In the case of OFF2 and OFF3, the motors connecting to the line are switched off immediately with the OFF
command(same behavior as with p29533=0).Then the converter controlled motor is ramp down following OFF2 or
OFF3 behavior.
Value:
0:
Halt normal
1:
Halt sequential
Parameters
7.2 Parameter list
SINAMICS G120X converter
918
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......