Note
Missing output load is signaled in the following cases:
- the motor is not connected.
- a phase failure has occurred.
p2180[0...n]
Output load detection delay time / Out_load det t_del
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8022
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
2000 [ms]
Description:
Sets the delay time for the message "output load not available" (r2197.11 = 1).
Dependency:
See also: p2179
p2181[0...n]
Load monitoring response / Load monit resp
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
0
Max:
8
Factory setting:
0
Description:
Sets the response when evaluating the load monitoring.
Value:
0:
Load monitoring disabled
1:
A07920 for torque/speed too low
2:
A07921 for torque/speed too high
3:
A07922 for torque/speed out of tolerance
4:
F07923 for torque/speed too low
5:
F07924 for torque/speed too high
6:
F07925 for torque/speed out of tolerance
7:
Pump/fan load monitoring as alarm
8:
Pump/fan load monitoring as fault
Dependency:
See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, p2193, r2198, p3230, p3231
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925
Note
The response to the faults F07923 ... F07925 can be set.
This parameter setting has no effect on the generation of fault F07936.
p2181 = 7, 8 can only be combined with p2193 = 4, 5.
p2182[0...n]
Load monitoring speed threshold value 1 / n_thresh 1
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8013
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
150.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
785
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......