0:
DI0
1:
DI1
2:
DI2
3:
DI3
4:
DI4
5:
DI5
Note
On variants with PN/DP interface, ON/OFF2 is disabled as default(p29650=-1), when enabled(p29650>=0), the
configuration of p840 and p844 will not be updated internally. ON/OFF2 is only effective if both are configured as r29659
bit0 and bit1 respectively.
p29651[0...n]
BI: ON/OFF1 (OFF1) / ON/OFF1 (OFF1)
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the command "ON/OFF1 (OFF1)".
p29652[0...n]
BI: ON/OFF2 (OFF2) / ON/OFF2 (OFF2)
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the command "ON/OFF2 (OFF2)".
r29659.0...1
CO/BO: Command word / Cmd word
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Command status is for ON/OFF1, OFF2 which can connect to p0840, p0844.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Active
Inactive
-
01
coast-down(OFF2) signal source
Active
Inactive
-
p29700[0...n]
Temperature sensor type / TempSen type
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Description:
Sets the sensor type for temperature measurement.
This means that the temperature sensor type is selected and the evaluation is switched in.
Value:
0:
Evaluation disabled
1:
1 x PT100
2:
2 x PT100
Parameters
7.2 Parameter list
SINAMICS G120X converter
932
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......