r1614
EMF maximum / EMF max
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: 5_1
Unit selection: p0505
Function diagram: 6725
Min:
- [Vrms]
Max:
- [Vrms]
Factory setting:
- [Vrms]
Description:
Displays the actual maximum possible electromotive force (EMF) of the separately excited synchronous motor.
Dependency:
The value is the basis for the flux setpoint.
The maximum possible EMF depends on the following factors:
- Actual DC link voltage (r0070).
- Maximum modulation depth (p1803).
- Field-generating and torque-generating current setpoint.
p1616[0...n]
Current setpoint smoothing time / I_set T_smooth
Access level: 3
Calculated: CALC_MOD_REG Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6721, 6722
Min:
4 [ms]
Max:
10000 [ms]
Factory setting:
40 [ms]
Description:
Sets the smoothing time for the current setpoint.
The current setpoint is generated from p1610 and p1611.
Note
This parameter is only effective in the range where current is injected for sensorless vector control.
r1623[0...1]
Field-generating current setpoint (steady-state) / Id_set stationary
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 6723
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Displays the steady-state field generating current setpoint (Id_set).
Note
For index 1:
Reserved.
r1624
Field-generating current setpoint total / Id_setp total
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 6640, 6721,
6723, 6727
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Displays the limited field-generating current setpoint (Id_set).
This value comprises the steady-state field-generating current setpoint r1623 and a dynamic component that is only
set when changes are made to the flux setpoint.
Parameters
7.2 Parameter list
SINAMICS G120X converter
698
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......