Data block
Byte n
Bytes n + 1
n
Address, parameter 1
Attribute
10 hex:
Parameter value
20 hex:
Parameter description
Number of the indices
00 hex ... EA hex
(For parameters without index: 00 hex)
4
Parameter number
0001 hex ... FFFE hex
6
Number of the 1st index
0000 hex ... FFFF hex
(for parameters without index: 0000 hex)
8
…
…
Address, parameter 2
…
…
…
…
…
Address, parameter m …
…
Table 6-14
Converter response to a read request
Data block
Byte n
Bytes n + 1
n
Header
Reference (identical to a read request)
01 hex: Converter has executed the read re‐
quest.
81 hex: Converter was not able to completely
execute the read request.
0
01 hex (ID of drive objects, at G120 always = 1) Number of parameters (m)
(identical to the read request)
2
Values, parameter 1
Format
02 hex
: Integer8
03 hex
: Integer16
04 hex
: Integer32
05 hex
: Unsigned8
06 hex
: Unsigned16
07 hex
: Unsigned32
08 hex
: FloatingPoint
0A hex
: OctetString
0D hex
: TimeDifference
34 hex
: TimeOfDay without date indication
35 hex
: TimeDifference with date indication
36 hex
: TimeDifference without date indication
41 hex
: Byte
42 hex
: Word
43 hex
: Double word
44 hex
: Error
Number of index values or - for a negative re‐
sponse - number of error values
4
Value of the 1st index or - for a negative response - error value 1
You can find the error values in a table at the end of this section.
6
…
…
Values, parameter 2
…
…
…
Values, parameter m
…
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
221
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......